MX/QX FOUNDATION Fieldbus Field Unit FCD LMENIM2330-01 – 08/11
flowserve.com
2.6.2.2 Network Cable Connections to Other Network Components
Each FOUNDATION fieldbus network may require some or all of the following components depending
on the application:
Junction Box/Terminal Blocks
Connectors
Power Supplies
Power Conditioners
Terminators
Intrinsic Safety Barriers
Bridge and Repeaters
For cable connecting information on these components, see the following:
FOUNDATION Fieldbus Wiring and Installation 31.25 kbits/s, Voltage Mode, Wire Medium AG-140
Relcom Inc. Fieldbus Wiring Design and Installation Guide
ANSI/ISA-S50.02, Part 2-1992, Fieldbus Standard for Use in Industrial Control Systems Part 2:
Physical Layer Specification and Service Definition
2.6.2.3 Cable Length and Number of Devices Requirements
The network cable consists of a trunk, segments, and spurs. The trunk is the main connection
between all the devices. A segment is a section of the cable that contains the terminators. A spur
connects to the trunk through a junction box. The following topologies are possible:
Point-to-point
Bus with Spurs
Daisy Chain
Tree topology
Combination of the above
Figure 2.15 – Network with Spurs
T
Fieldbus
I/O
Control Highway
DCS
(Host)
Terminator
Junction
Box
Fieldbus Trunk
Spur
Spur
T
Terminator
MX/QX FF
Actuator
MX/QX FF
Actuator
MX/QX FF
Actuator
MX/QX FF
Actuator