PB DPV1 / PA Field Unit Installation and Maintenance FCD LMENIM2336-03 – 12/12
66
Channel 351 – Actuator Alarms (Index 111)
This channel, DI_ACTUATOR_ALARMS_CHAN, makes actuator alarms available to other function
blocks. The alarms include:
• Local emergency shutdown has occurred; the field unit will command the actuator to go to a pre-
configured position, or stop, or ignore the ESD.
• Remote emergency shutdown has been received from the network host; the field unit will
command the actuator to go to a pre-configured position, or stop, or ignore the ESD.
• Open inhibit is active.
• Close inhibit is active.
Channel 351
DI_ACTUATOR_ALARMS_CHAN Value
Local ESD Active 0x01
Remote ESD Active 0x02
Open Inhibit Active 0x04
Close Inhibit Active 0x08
Local ESD Active + Open Inhibit Active 0x05
Local ESD Active + Close Inhibit Active 0x09
Remote ESD Active + Open Inhibit Active 0x06
Remote ESD Active + Close Inhibit Active 0x0A
Open Inhibit Active + Close Inhibit Active 0x0C
Channel 352 – Discrete User Input (Index 112)
This channel, DI_DISC_USER_INPUT_CHAN, makes general-purpose contact inputs available to other
function blocks. The functions in the table, such as ESD, must be configured to the OFF state locally
in the MX/QX PB setup menus in order to use the inputs as general-purpose inputs. Functions, such
as ESD, when configured to OFF, are not enabled. Refer to the following sections in MX Installation &
Operation Manual, LMENIM2306, and QX Installation & Operation Manual, LMENIM3306:
• Section 4.15 – ESD – Emergency Shutdown
• Section 4.16 – Inhibits – Open/Close Inhibit
• Section 4.13 – Remote Control – Open/Close/Stop Pushbutton Inputs
This channel places each discrete input bit value to 0 if the discrete input is not enabled.
Channel 352
DI_DISC_USER_INPUT_CHAN Terminal #
Alt
Function
Value
User Input Number 0 30 ESD Open Bit 0
User Input Number 1 34 Open Inhibit Bit 1
User Input Number 2 35 Close Inhibit Bit 2
User Input Number 3 26 Stop PBS Input Bit 3
User Input Number 4 25 Open PBS Input Bit 4
User Input Number 5 27 Close PBS Input Bit 5