Installation
Control unit NRS 1-40.1
When changing the default factory settings (see page 16 and 17) the following steps:
Change baud rate,
Change configuration (see section “Commissioning“) and
Change node ID (see section “Annex“)
must be carried out before mounting the equipment. Make sure that the terminal strips
are unplugged before performing the work in a single operation.
Change settings
1. Unplug the upper and lower terminal strips . (see Fig.4)
2. The terminal strip can be unplugged after undoing the right and the left fixing screws .
3. Set code switch and as required.
4. Re-insert terminal strips and fasten the fixing screws .
Mount control unit
The control unit NRS 1-40.1 is clipped onto a support rail type TH 35, EN 60715 in the control cabinet.
(see Fig. 4)
Tools
Screwdriver (5.5/100)
Note
A
B
C
D E
A B C
G