User InterfaceManualUser Instructions StarPac II Control Valves FCD VLAMN042-01
7. Using the Command % option in the TUNE menu, enter a 100 percent command and verify that the position follows to within 0.5 percent. 8. If the u
Status Menu The STATUS menu is used to view information about the configuration and operation of the system. Errors and alarms can also be viewed f
Totalizer Time - Operating time since the totalizer was last reset. (Designated as “TotTm” in the display.) Valve Cv - Current valve CV at present v
Alarms - Allows the user to view any current alarms using the NEXT or PREVIOUS function keys. Possible alarms are: Setpoint Deviation - The controll
persists. This error can only be cleared by turning off the device and then turning it on again. EPROM Checksum Error - Check the integrity of the fi
Override Condition - Indicates the controller is currently not capable doing any more to achieve the setpoint (or valve position). This can be any o
Man/Auto - This option selects or changes the operating mode if the mode source has been set to digital. If the mode source is set to Remote or Disc
Remote Refresh Rate - This option sets up a time-out on the receipt of fresh setpoint data when set to operate with a remote setpoint. If the setpoi
Process Variable Air-to-Open Valve Air-to-Close Valve Flow Reverse Direct Upstream Pressure Direct Reverse Downstream Pressure Reverse Direct
WARNING: Taking the StarPac II unit off line may cause the valve to stroke unexpectedly. Notify personnel working nearby that the valve may stroke.
source should be connected to terminals 24(-) and 25(+) of the terminal block. The display will give instructions to adjust the signal until the ref
the individual calibration options. Because the valve will change position during this process, you must confirm that you want to proceed. You will
thermocouple simulator connected to terminals 5 (yellow) and 6 (red). Zero - Apply a signal equal to the minimum temperature you want to use for your
the valve is forced to full open and full closed by driving the positioner output to its maximum and minimum values. WARNING: Notify personnel worki
ISA Dn Stream Press - Current compensated downstream line pressure (defined as six pipe diameters downstream of the valve). ISA Delta Pressure - Curr
will open the valve at the selected rate. (Note that this value may be set different from the spring failure of the actuator.) Analog In 2 - This op
Air Action - Used to set up the StarPac II for the configured actuator failure mode. ATO (Air-to-Open) is normally used for fail-closed valves, ATC
Process Pressure - This option sets the process pressure engineering units for the StarPac II system. Use the NEXT and PREVIOUS function keys to sel
the name that you want the totalizer to display for the totalized units. Process Temperature - Sets the process temperature engineering units for th
NextPassWordAddressBaudRateCommPortLCDContPar-ityNextRTU/ASCIPortAccsTXDlyFigure 9: Comm Port Menu Address - This option sets the Modbus address of
StarPac II User Interface Manual StarPac II User Interface Manual
LCD Backlight - Use this option to set the time that the backlight in the LCD will stay on after the last pressed key. Available options are: Always
recommended that you use the StarTalk for windows software to reload your system information from the factory supplied disk. Data Logger - This optio
FK coefficient (=K/1.4) register 70345 Molecular Weight register 70347 Specific Gravity Reference temp in ºR register 70349 Specific Gravity
position, the jumper configures the relay to Normally-closed operation. Discrete Input Range Selection - Under the personality card are two sets of t
Appendices System Setup Checklist A. Power • (24) VDC power at least 300 mA. • Polarity correct. • Local display ON. If not, check power supply. B
Detailed StarPac ll Register Map This reference will aid you in understanding the configuration of the StarPac ll register table. Registers are des
Integer Register Attribute Description Notes 30014 RO ADC value being output by the position feedback Hallpot. Range -32767 to 32767. 30015 RO A
Integer Register Attribute Description Notes 30029 RO External 115V accessory A&B on/off input status. 0 = A&B on. (BCD220) 1 = A of
Integer Register Attribute Description Notes 40036 RW Atmospheric pressure unit selection. 40 = psig 41 = psia 42 = kPa g 43 = kPa a 44 = kg/sq
Integer Register Attribute Description Notes 40047 RW Scaled setpoint command. Range 0 to 9999, with fixed scale range -12.5 to 112.5 percent. 4
Integer Register Attribute Description Notes 40064 RW Maximum ADC value corresponding to 185 °F ambient temperature. Range -32768 to 32768 40065
Integer Register Attribute Description Notes 40081 RW Reset integer scaler flag. Range 0 to 1. Writing a value of 1 to this register causes the
Integer Register Attribute Description Notes 40094 RW Variable number for liquid flow scaling factor input to be used in flow calculation. Range -
Integer Register Attribute Description Notes 40105 RW Variable number of output No. 10 to be displayed on Local display. Range -1 to 1023. Writin
Integer Register Attribute Description Notes 40115 RW Communication port access. Bit field Bit Meaning 0= A-RW B-RW 1= A-RW B-RO 2= A-RO B-RW 40
Floating Point Registers Notice that floating point register numbers go up by two instead of up by one. This is because floating point registers c
Floating Point Register Attribute Description Notes 70253 RO Output from position Hallpot in percent. 70255 RO 4-20 mA analog auxiliary signal
Floating Point Register Attribute Description Notes 70299 RW Gas flow in selected units used to output 20 mA on analog output channel. Range .1 to
Floating Point Register Attribute Description Notes 70331 RW Antoine B fluid coefficient. Range 0 to 1.0E6. Used to calculate the fluid vapor pre
Floating Point Register Attribute Description Notes 70383 RW CV D1 curve fit coefficient. Range -1.0E9 to 1.0E9. 70385 RW CV E1 curve fit coeffici
Contents OPERATION Getting Started ……………..……………………….. 1 StarPac II Local Interface Structure & Operation .. 2 Initial Startup………..……………………………
Floating Point Register Attribute Description Notes 70459 RW XT D2 curve fit coefficient. Range -1.0E9 to 1.0E9. 70461 RW XT E2 curve fit coeffici
Floating Point Register Attribute Description Notes 70495 RW Step time value in seconds. Range 1 to 20. Valve will move to the stopping position
Floating Point Register Attribute Description Notes 70521 RO Signature/Logger auxiliary 4-20 mA input data in percent. This value is loaded from de
Floating Point Register Attribute Description Notes 70579 RW user units = 20mA at DAC#1 70581 RW user units = 4mA at DAC#1 70583 RW Full-sc
String Registers The register numbers in this table are not consecutive because of the varying length of each string in this area of StarPac
String Register Attribute Description Notes 50833 RW Spring type used in actuator on this system. ASCII characters. 16 bytes. 50841 RW Air acti
Fluid Table Name Critical Press Critical Temp Temp Ref Spec Gr Mol Wt Spec Heat RatioAnt A Ant B Ant C ViscA Visc B AIR 492.445007 227.160004
StarPac Wiring and Grounding Guidelines This guideline will help you in achieving maximum noise rejection and performance with a StarPac Intelligent
StarPac II User Interface Manual 52 4-20 mA Command Input, Auxiliary Input, and Feedback Output These signals are isolated but shielded twisted pai
Index —A— Actuator air action, 19 pressure sensor calibration, 14 stroke, 14 Air supply trip configuring, 20 Alarms masking, 8 viewing, 6 Analog comm
Operation Getting Started This manual is designed to help you become familiar with, and efficiently operate, the StarPac® II Intelligent Control Sys
StarPac II Local interface Structure & Operation The StarPac II local user interface allows complete user access to configure and calibrate a Sta
the figures shows the bottom two rows of the display. One of the fields is in Bold type. Press the F key under this field to bring up the choices s