MEN
USER INSTRUCTIONS ENGLISH 71576288 – 11-09
Page 22 of 36
®
The "CLEAR DEFAULT" turn-key button is not
working as long as the fault is present. If it is
activated, it re-initiates the audible alarm.
When the engine is operating, the engine water
reheating is inhibited.
Mains cut-off lights up the reheating fault LED.
Engine water level control:
In case of low cooling water level in the engine, the
"ENGINE WATER LEVEL" red LED lights up and the
siren and the "FAILURE RISK" relay and plant
start-up are activated.
The siren can be stopped by pressing the "STOP
SIREN" pushbutton. But this does not clear the fault
which is reported on the alarm base station.
The "CLEAR DEFAULT" turn-key button is not
working as long as the fault is present. If it is
activated, it re-initiates the audible alarm.
Priming tank level control (optional):
In case of low water level in priming tank, the
"PRIMING TANK LEVEL" red LED lights up and the
siren and the "FAILURE RISK" relay are activated.
The unit then starts.
The siren can be stopped by pressing the "STOP
SIREN" pushbutton. But this does not clear the fault
which is reported on the alarm base station.
Check that the priming tank level is correct and stop
the unit using the STOP handle on the engine.
The "CLEAR DEFAULT" turn-key button is not
working as long as the fault is present. If it is
activated, it re-initiates the audible alarm and
restarts the motor pump if the level is not correct.
Control of pressure switch line:
In the case of a short circuit on the pressure switch
connection cables, the warning light "Pressure
Switch Line" lights up, and the alarm and "Risk of
failure" relay are activated.
The siren can be stopped by pressing the "STOP
SIREN" pushbutton. But this does not clear the fault
which is reported on the alarm base station.
The "CLEAR DEFAULT" turn-key button is not
working as long as the fault is present. If it is
activated, it re-initiates the audible alarm.