Worcester Actuation SystemsWCAIM2029(Part 16022)Series F75 Fail-Safe ModuleInstallation, Operation and Maintenance InstructionsCAUTION: Flowserve reco
2 Series F75 Fail-Safe Module WCAIM20292.2 Proper wire size should be selected from the table below for DCpower wiring between Series F75 Module and a
3. TESTINGThe instructions below use directional conventions established forstandard wiring.Once the Series F75 Module has been wired to the actuator,
4 Series F75 Fail-Safe Module WCAIM20296. BATTERIES6.1 To obtain optimum shelf life, batteries should be stored in a coolarea; if possible, store batt
WCAIM2029 Series F75 Fail-Safe Module 57.3 TroubleshootingSymptom Check Results1. Unit has switched to the fail-safe mode. No Operate panel “Reset”
6 Series F75 Fail-Safe Module WCAIM20299. SPARE PARTSThe following are recommended spare parts that should be kept onhand for Series F75 Fail-safe Mod
WCAIM2029 Series F75 Fail-Safe Module 7Flow Control DivisionWorcester Actuation Systems Figure 3CAUTION:Figure 4 – Section B-BEagle-Picher Batteries S
Flow Control DivisionWorcester Actuation Systems Flowserve Corporation has established industry leadership in the design and manufacture of its produc