6. Connect the network cables to the MX terminal block as shown in Figure 3.6. Table 3.3 defines each network cable
termination. Refer to Figure 3.8 and 3.9 for topology-specific wiring connections.
Table 3.3 – Network cable terminations
Terminal Block Number Function
4 NETWORK
5 NETWORK
14 NETWORK
13 NETWORK
3 NETWORK SURGE (EGND)
NOTE: Ground each segment of the cabling at only one point to prevent ground loops, which can affect system
performance. Verify the actuator is properly grounded.
7. Install jumper cable from terminal block pin 3 to earth ground or ground lug.
Figure 3.7 – Connecting network cable to MX terminal block